The 50V51-843 has only one serviceable part –an automotive
type fuse, which protects the low voltage transforme
r from
dam
age if the output is short-circuited. If the fuse has opened
up, remove whatever caused the short circuit and replace the
fuse with only a 3 Amp automotive type fuse. If the fuse does
not correct the condition, replace the entire 50V51 control. There
are not other user serviceable parts.
Following installation or replacement, follow appliance manu-
facturer’s recommended installation or service instructions to
insure proper operation.
INSTALLER MUST READ FOR PROPER
INSTALLATION
• Wiring harnesses are included to complete the installation of
the “UNIVERSAL 50V51-843” for Goodman applications.
• For replacing the ignitor, a UNIVERSAL 21D64-2 is included.
For proper installation, refer to the instructions included in
the 21D64-2 kit.
• IMPORTANT: The installer may have to enlarge existing igni-
tor hole to accommodate 21D64-2 larger (.394”) diameter.
SYSTEM LOCKOUT
When a system lockout occurs (1hour), the gas valve is de-
energized, the low speed inducer blower is energized for the
60 second interpurge period and the circulator is energized for
selected heat off delay if it was previously ON. The diagnostic
indicator light will flash the fault that is present (refer to diag-
nostic table).
MOUNTING AND WIRING
All wiring should be installed according to local and national
electrical codes and ordinances.
The control must be secured to an area that will experience a
minimum of vibration and remain below the maximum ambient
temperature rating of 175°F. The control is approved for minimum
ambient temperatures of -40°F.
Any orientation is acceptable.
Refer to the wiring diagram and wiring table when connecting
the 50V51 control to other components of the system.
UL approved, 105°C rated 18 gauge min., stranded, 2/64” thick
insulation wire is recommended for all low voltage safety circuit
connections. Refer to 50V51 specification sheet for recom-
mended terminals to mate with those on the control.
UL approved, 105°C rated 16 gauge min., stranded, 4/64” thick
insulation wire is recommended for all line voltage connections.
Refer to 50V51 specification sheet for recommended terminals
to mate with those on the control.
GOODMAN NOTE
FOR GOODMAN 50V51-289 APPLICATION, THERE
ARE TWO ADAPTER HARNESSES INCLUDED IN THIS
PACKAGE TO COMPLETE THE INSTALLATION.
To reset the control after system lockout, do one of the
following:
System Reset
Remove 24 VAC power to the control for twenty (20) seconds
or longer to reset the control.
Thermostat Reset
Remove the call for heat from the thermostat for a period of
between (1) second and less 20 seconds. If flame is sensed
with the gas valve de-energized, interrupting the call for heat
at the thermostat will not reset the control.
Auto Restart
After one (1) hour of internal or external lockout, the control
will automatically reset itself and go into an auto restart purge
for 15 seconds.
DIAGNOSTIC FEATURES
The control continuously monitors its own operation and the op-
eration of the system. If a failure occurs the diagnostic indicator
LED (DSI) will flash a “RED” failure code. If a failure is internal
to the control the “RED” indicator will stay on continuously.
In this case, the entire control should be replaced as the
control is not field-repairable. If the LED is continuously OFF,
there may be no power to the control or a failure within the con-
trol. If the sensed failure is in the system (external to the control),
the LED will flash RED in the sequence listed in the Diagnostic
Table. The LED will also indicate “System Status” as per the
Amber and Green LED signatures listed in the Diagnostic Table.
The LED will flash one RED flash at power up.
CFM INDICATOR
The LED (DS2) CFM flashes when the blower motor is running.
The flashing indicates the motor CFM (cubic feet per minute)
air flow designated by the furnace manufacturer. Consult the
furnace manufacturer for flash code detail.
FAULT CODE RETRIEVAL
To retrieve fault codes, push and release the “LAST ERROR”
button for more than 1/5 second and less than 5 seconds. (Con-
trol will indicate this period by solid GREEN for 1/5 secs. to 5
secs.). The LED will flash up to five stored fault codes, beginning
with the most recent. If there are no fault codes in memory, the
LED will flash two green flashes. The control will
flash the most recent error first and the oldest error last (last in
first out). There shall be 2 seconds between codes. Solid LED
error codes will not be displayed.
NOTE
These error codes may be different from furnace label or
furnace manual.
INTEGRATED
FURNACE CONTROLS
21V51U-843
OPERATION
TECHNICAL HELP
www.white-rodgers.com
187