21V51U-843
OPERATION
INTEGRATED
FURNACE CONTROLS
Heat Fan Off Delay Timing
DIP switches S7-3 and S7-4 (see table above) configure
the number of seconds the blower will run after the call
for heat ends. Factory default is 90 seconds.
OPTION SWITCH SETTING – FURNACE
MANUFACTURER
OPTIONS SWITCHES
Option switches are used to determine the length of the delay
periods. The following tables show the time periods that will
result from the various switch settings.
OPTION SWITCH SETTING - THERMOSTAT
TYPE AND HEAT-FAN-OFF-DELAY
Multi-stage Thermostat Set-up,
Factory Default
DIP switches S7-1 and S7-2 (see table above) are set to the
“Off” position from the factory for use with a multi-stage ther-
mostat. This allows the thermostat to control staging between
low and high fire.
Single Stage Thermostat Set-up,
Module Controls Staging
DIP switches, S7-1 and S7-2 (see table above) configure for a
single stage thermostat. Options include a 10 minute delay on
second stage, 20 minute delay on second stage or an Auto set-
ting allowing the module to calculate the time delay for second
stage based on average demand. The “Average Calculated
Duty Cycle” table shows how the module calculates staging
based on demand.
Average
Calculated
Duty Cycle
% Equals
or is less
than
Low to High
Stage Delay Demand
0 38 12 minutes Light
38 50 10 minutes Light to Average
50 62 7 minutes Average
62 75 5 minutes Average to Heavy
75 88 3 minutes Heavy Light
88 100 1 minute Heavy
DIP Switches
Switch Settings Options
Thermostat
Type and W2
Delay S7-1,
S7-2
S7-1 S7-2 Time
Off Off Off*
On Off 10 Minutes
Off On Auto
On On 20 Minutes
Heat Fan Off
Delay
S7-3, S7-4
S7-3 S7-4 Time
Off Off 90 Secs*
Off On 120 Secs
On Off 150 Secs
On On 180 Secs
*Factory Settings
S7
3
4
1
2
OFF ON
DIP Switches
Switch
Settings
Options
Heat Pump
S5-1
S5-1
Off Installed
On Not Installed*
De-humidifier
S5-2
S5-2
Off Installed
On Not Installed*
*Factory Settings
S5
1
2
OFF ON
IMPORTANT: Switch selection must match furnace
manufacturer for proper motor operation.
Set DIP switches S2-1 and S2-2 to match the equipment using
the table above. NOTE: DIP switch S2-3 is not used.
DIP Switch Selection for OEM Applications
S2
OEM
12
OFF OFF Trane
OFF ON
Thermo Pride/
Goodman
ON OFF Lennox
ON ON York
3
1
2
OFF ON
S2
OPTION SWITCH SETTING - HEAT PUMP
AND DE-HUMIDIFICATION
Heat Pump Systems
DIP switch S5-1 (see table above) is set to “On” from the factory
for use with conventional (non-Heat Pump systems). For heat
pump systems move the S5-1 DIP switch to the “Off” position.
This will continuously output an O signal to the motor whenever
there is Y signal and run the circulator blower at a constant
speed when the pump is operating.
De-Humidification Connection
DIP switch S5-2 (see table above) is set to “On” from the fac-
tory for systems that do not have a dehumidification terminal
connection from the thermostat. For systems using a thermostat
that provides a De-Humidification option move DIP switch S5-2
to “Off”.