INTEGRATED
FURNACE CONTROLS
21M51U-843
OPERATION
TWINNING INTERFACE
The 50M51 is equipped with a single wire twinning interface.
If twinning is used, either control will process a call for heat,
cool or fan as described previously. However, after the heat- or
cool-on delay time expires, both units will energize the circulator
blowers at the same time. Likewise, after the heat- or cool-off
delay time expires, both units will de-energize the circulator at
the same time. This allows for the proper air flow to be obtained.
In a twinned application, the controls are able to communicate
no matter how the transformers are phased.
To enable twinning, connect the TWIN screw terminals on the
50M51 controls of the furnaces to be twinned to each other
using a single wire (14-22 AWG).
SYSTEM LOCKOUT AND DIAGNOSTIC FEATURES
SYSTEM LOCKOUT
When system lockout occurs, the gas valve is de-energized and
the low speed inducer blower and the low heat speed circula-
tor are energized. The electronic air cleaner (optional) will also
energize at this time. The diagnostic indicator light will flash to
indicate the system status.
To reset the control after system lockout, do one of the
following:
1. Interrupt the call for heat at the thermostat for at least one
second but less than 20 seconds (if flame is sensed with
the gas valve de-energized, interrupting the call for heat at
the thermostat will not reset the control).
2. Interrupt the 24 VAC power at the control for at least 20
seconds. You may also need to reset the flame rollout sen-
sor switch.
3. After one hour in lockout, the control will automatically reset
itself.
LAST FAULT MODE
To retrieve fault codes, push and release the "LAST ERROR"
button for more than 1/5 second and less than 5 seconds.
(Control will indicate this period by solid GREEN for 1/5 to
5 seconds). The LED will flash up to five stored fault codes,
beginning with the most recent. If there are no fault codes in
memory, the LED will flash two green flashes. The control will
flash the most recent error first and the oldest error last (last in
first out). There shall be 2 seconds between codes. Solid LED
error codes will not be displayed.
FAULT CODE RESET
To clear the fault code memory, push and hold the "LAST ER-
ROR" button for more than 5 seconds and less than 10 seconds.
(Control will indicate this period by RAPID GREEN FLASH for 5
seconds to 10 seconds.) The LED will flash three green flashes
when the memory has been cleared.
DIAGNOSTIC FEATURES
The 50M51 control continuously monitors its own operation
and the operation of the system. If a failure occurs, the red
LED on the control will flash a failure code. If the failure is
internal to the control, the light will stay on. In this case,
the entire control should be replaced, as the control is not
field-repairable.
If the sensed failure is in the system (external to control), the
LED will flash in the following flash-pause sequences to indicate
failure status (each flash will last approximately 0.25 seconds,
and each pause will last approximately 2 seconds.)
During a second-stage error condition, the red LED when in
lockout will flash groups of double pulses. The red LED will flash
on for approximately 1/15 second then off for 1/15 second then
on for 1/15 second, then off for 3/10 second. The pause between
groups of flashes is approximately 2 seconds.
The diagnostics will indicate the specific fault through the fol-
lowing codes:
COOL MODE
In a typical single stage cooling system (Y connection), a call for
cool is initiated by closing the thermostat contacts. This energizes
the compressor and the electronic air cleaner (optional).
The circulator will be energized at cool speed after the COOL
delay-to-fan-on period. After the thermostat is satisfied, the
compressor is de-energized and the COOL delay-to-fan-off
period begins. After the COOL delay-to-fan-off period ends, the
circulator and the electronic air cleaner are de-energized.
MANUAL FAN ON MODE
If the thermostat fan switch is moved to the ON position, the
circulator fan (low heat speed) and the electronic air cleaner
(optional) are energized. When the fan switch is returned to
the AUTO position, the circulator and electronic air cleaner are
de-energized.
TECHNICAL HELP
www.white-rodgers.com
181