WIRING DIAGRAM 4 - HVAC Equipment – Conventional
Two Stage Heating and Single Stage Cooling
Y1 FIRST STAGE COOL
G FAN RELAY
R 24VAC TRANSFORMER C
W1 FIRST STAGE HEAT RELAY
W2 SECOND STAGE HEATING RELAY
Y1
G
O
W1/B
R
W2
W3/E
WIRING DIAGRAM 5 - Single Speed Compressor
Heat Pump
.
Y COMPRESSOR RELAY
G FAN RELAY
O REVERSING VALVE COOL
B REVERSING VALVE HEAT
R 24VAC TRANSFORMER C
W2 SECOND STAGE HEAT
E EMERGENCY HEAT
Y1
G
O
W1/B
R
W2
W3/E
WIRING DIAGRAM 6 - Two Speed Compressor Heat Pump
FIRST STAGE COMPRESSOR
FAN RELAY
REVERSING VALVE COOL
REVERSING VALVE HEAT
R 24VAC TRANSFORMER C
THIRD STAGE/EMER HEAT
SECOND STAGE
COMPRESSOR
Y1
G
O
W1/B
R
W2
W3/E
TROUBLESHOOTING
The CMM-3U is a very simple control to troubleshoot, especially with
the LED indicators. The only other device needed is a simple Volt/
Ohm meter. Almost all problems can be traced to an external com-
ponent or wiring to the CMM-3U. The following procedures can help
isolate the problem.
Zone(s) Not Calling
Each zone has a Green LED next to the zone relay when it is calling
and that calling is being recognized by the CMM-3U. If a zone is
supposed to be calling and the Zone LED is not on, check for 24VAC
across the thermostat terminal C and the Y, if a Cool call, W if a Heat
Call, or G if a Fan call. If there is no voltage here at the panel the
panel is not getting the signal from the thermostat. The problem is
mis-wiring, a broken wire or a problem in the thermostat. To check
the zone on the panel, place jumper from R to Y, R to W or R to G to
see that the panel is operating properly.
Zone(s) Will Not Shut Off
If a zone will not stop calling, the Zone LED should still be on. De-
pending on the call disconnect the Y, W or G wire from the terminal
strip. The zone will drop out. Check the thermostat wiring for a mis-
wiring or short that keeps the zone calling.
Damper Motor Checkout
To checkout the dampers, the panel provides 24VAC to the COM
and OPEN when the damper is to be open and 24VAC to COM and
CLOSE when the damper is to be CLOSED. When any zone is
calling and its Green LED is ON, there is 24VAC across COM and
OPEN. The only time a damper will close is when anther zone is
calling and its zone is not calling. In this instance there will be 24VAC
across COM and CLOSE.
ZONE PANEL
CMM-3U
CMM-3UK
www.white-rodgers.com
254
TECHNICAL HELP