DIAGNOSTIC TABLE
Green
LED
Flash
Amber
LED
Flash
Red LED
Flash Error/Condition Comments/Troubleshooting
1 Flame sensed when no flame should be
present
Verify the gas valve is operating and shutting down properly. Flame in burner
assemble should extinguish promptly at the end of the cycle. Check orifices
and gas pressure.
2 Pressure switch stuck closed/ inducer error Pressure switch stuck closed. Check switch function, verify inducer is turning
off.
3 1st-stage pressure switch stuck open/inducer
error
Check pressure switch function and tubing. Verify inducer is turning on the
pulling sufficient vacuum to engage switch.
4 Open limit switch Verify continuity through rollout switch circuit.
5 Open rollout/open fuse detect Verify continuity through rollout switch circuit, check fuse.
6 1st-stage pressure switch cycle lockout if the first stage pressure switch cycles 5 times (open, closed) during one call
for heat from the thermostat the control will lockout. Check pressure switch for
fluttering, inconsistent closure or poor vacuum pressure.
7 External lockout (retries) Failure to sense flame is often caused by carbon deposits on the flame
sensor, a disconnected or shorted flame sensor lead or a poorly grounded
furnace. Carbon deposits can be cleaned with emery cloth. Verify sensor is not
contacting the burner and is located in a good position to sense flame. Check
sensor lead for shorting and verify furnace is grounded properly.
8 External lockout (ignition recycles exceeded
where flame is established and then lost)
Check items for exceeded retries listed above and verify valve is not dropping
out allowing flame to be established and then lost.
9 Grounding or Reversed polarity Verify the control and furnace are properly grounded. Check and reverse
polarity (primary) if incorrect.
10 Module gas valve contacts energized with no
call for heat
Verify valve is not receiving voltage from a short. If a valve wiring is correct and
condition persists, replace module.
11 Limit switch open – possible blower failure
overheating limit
Possible blower failure, restricted air flow through appliance or duct work. Verify
continuity through limit switch circuit and correct overheating cause.
12 Module Ignitor contact failure Fault code indicates the module ignitor contacts are not functioning properly.
Replace module.
Solid Module - internal fault condition Module contacts for gas valve not operating or processor fault. Reset control. if
condition persists replace module.
Rapid Twinning error Check wire connections. If condition persists, replace module.
3 double 2nd-stage Pressure Switch Stuck Open/
Inducer Error
Check pressure switch function and tubing. Verify inducer is turning on and
pulling sufficient vacuum to engage switch.
1 Normal Operation with call for first stage heat Normal operation - first stage
2 Normal Operation with call for second stage
heat
Normal operation - first stage
3 W2 present with no W1 Second stage call for heat on thermostat circuit with no call for first stage.
Verify dip switches are set for two stage thermostat and check thermostat first
stage circuit. Configured for a multi-stage thermostat the Module will not initiate
heating unless first stage call from thermostat is received.
4 Y present with no G call Module will allow cooling to operate with only a "Y signal from the thermostat
but will also trigger this code. Verify thermostat is energizing both "Y" and "G"
on call for cool. Check "G" terminal connections.
Rapid Low flame sense current Low flame sense current is often caused by carbon deposits on the flame
sensor, a poorly grounded furnace or a mis-aligned flame sense probe. Carbon
deposits can be cleaned with emery cloth. Check for improve furnace and
module ground. Verify sensor is located in or very near flame as specified by
the appliance manufacturer.
1 Standby or Call for Cool Normal operation. Waiting for call from thermostat or receiving thermostat call
for cool.
INTEGRATED
FURNACE CONTROLS
21M51U-843
DIAGNOSTIC TABLE
www.white-rodgers.com
182